SIS logic solver: three types: relay system, programmable electronic system, and hybrid system;
Relays are used in situations with fewer I/O points and simple logical functions;
Programmable electronic systems are used in situations where there are many I/O points, complex logical functions, and communication with DCS, MES, etc;
Programmable electronic systems can be TUV certified PLC systems, as well as DCS and other specialized systems;
Principle of independent setting: Level 1 SIS logic solver should be separated from DCS;
Level 2 SIS logic solver should be separated from DCS;
Level 3 SIS logic solver must be separated from DCS;
Redundancy setting principle: Level 1 SIS can use a single logic solver;
Level 2 SIS should use redundant or fault-tolerant logic operators
The CPU power supply unit and communication unit should be configured with redundancy,
I/O modules should be configured with redundancy;
Level 3 SIS should use redundant fault-tolerant logic operators;
Among them, CPU power unit, communication unit, and I/O module
Redundant configuration should be provided;
I/O modules should be equipped with diagnostics and powered plug and drop;
SIS related on-site transmitters or final execution components shall be powered by the SIS system;
When the on-site transmitter signal is used for both SIS and DCS, it should be connected to the SIS system first and then to the
DCS system;
The sensors and final executing components connected to the I/O module should be designed as fault safe;
SIS should not use fieldbus communication method;