Call us 24/7+86 15359021002
Welcome to Shenzhen Changxin Automation Equipment Co., Ltd

FOXBORO FBM216B P0927AJ DCS system I/O module, available in stock

$299.00

In stock

Manufacturer: FOXBORO

model: FBM216B

Article number: P0927AJ

Telephone: +86 15359021002

Email: luckyXiao.909@Gmail.com

Transportation methods: UPS, DHL, FEDEX, TNT, ARAMEX, EMS

Payment method: Bank transfer or custody, PayPal or Western Union remittance. We accept payment in USD and RMB.

Delivery time: Some inventory parts can be shipped within 2 days. Some are reserved for 3-5 days. But high-power and special parts require 3-4 weeks.

SIS logic solver: three types: relay system, programmable electronic system, and hybrid system;

Relays are used in situations with fewer I/O points and simple logical functions;

Programmable electronic systems are used in situations where there are many I/O points, complex logical functions, and communication with DCS, MES, etc;

Programmable electronic systems can be TUV certified PLC systems, as well as DCS and other specialized systems;

Principle of independent setting: Level 1 SIS logic solver should be separated from DCS;

Level 2 SIS logic solver should be separated from DCS;

Level 3 SIS logic solver must be separated from DCS;

Redundancy setting principle: Level 1 SIS can use a single logic solver;

Level 2 SIS should use redundant or fault-tolerant logic operators

The CPU power supply unit and communication unit should be configured with redundancy,

I/O modules should be configured with redundancy;

Level 3 SIS should use redundant fault-tolerant logic operators;

Among them, CPU power unit, communication unit, and I/O module

Redundant configuration should be provided;

I/O modules should be equipped with diagnostics and powered plug and drop;

SIS related on-site transmitters or final execution components shall be powered by the SIS system;

When the on-site transmitter signal is used for both SIS and DCS, it should be connected to the SIS system first and then to the

DCS system;

The sensors and final executing components connected to the I/O module should be designed as fault safe;

SIS should not use fieldbus communication method;

    Customers reviews

    There are no reviews yet.

    Be the first to review “FOXBORO FBM216B P0927AJ DCS system I/O module, available in stock”

    Your email address will not be published. Required fields are marked *

    Search for products

    Back to Top
    Product has been added to your cart